product descriptions
FIRE ALARM & PROTECTION SOLUTIONS
FIRE ALARM & PROTECTION SOLUTIONS
Model | VEU-A00 |
Type | Analog type, 4 air intake inputs, maximum length of air pipe 400m |
Ambient temperature | 0 to 39℃ |
Verification temperature | -20 to 55℃ |
Relative Humidity | 10% to 95% |
Rated voltage | DC 24V |
Current consumption | monitoring 610 mA / alarm 650 mA |
Sensing | Measurement of the value of light scattering in the laser chamber by suctioning smoke particles with air intake pipes |
Ambient temperature | 0 to 39℃ |
Sampling air | -20 to 60℃ |
Test | -20 to 55℃ |
Relative Humidity | 10 to 95% |
Rated voltage | DC 24V |
Total piping length (including branch piping) | 800 m |
Maximum length per pipe, using 4 straight pipes | 100 m |
Dynamic sensitivity range | 0.0002%/m - 20% obs/m |
Sensitivity range | 0.001% - 20.0% obs/m |
Color | Silver |
Size | 350(W) × 225(H) × 135(D) mm |
IP rating | 40 |
Weight | 4.8 kg |
Relay | 7 programmable relays |
Accessory materials | VSP-962 / VSP-936 / VSP-964 |
Type approval number | 감19-75 |